Subsea flowline jumper failure releases ~16,000 bbl, Mississippi Canyon 209

A fractured subsea wellhead jumper (KAA-0120) connecting the MC 209 SS001 wellhead to a PLET released an estimated 16,000 barrels of oil while going undetected for several hours during start-up.

Source information

Source
Bureau of Safety and Environmental Enforcement
Investigating authority
Bureau of Safety and Environmental Enforcement
Report / reference no.
BSEE Panel 2019-002
Publication date
Dec 30, 2019
Last verified
Oct 4, 2026
BSEE record page (opens in new tab)

Event description

LLOG shut in Delta House on October 6, 2017 ahead of Hurricane Nate. During ramp-up on October 10–11, control room operators saw multiphase flow meter rates that did not match LACT meter rates; BSEE found the discrepancy was attributed to meter issues rather than a leak.

Source / investigation findings: BSEE

Probable / root cause

The failure resulted from internal corrosion within the jumper and mechanical stress added to the jumper from movement of the PLET and pipeline (BSEE panel conclusion).

Contributing factors

  • LLOG did not have any sensors in place that would alarm due to a suspected subsea leak; a PSL was installed but set below hydrostatic pressure.
  • Control room operators were not trained to shut in wells for unexplained pressure fluctuations or metering discrepancies.
  • BSEE found a prevalent mindset that meters are prone to malfunction and that subsea flowlines rarely fail.

Recommendations

  • Evaluate designs of applicable components for their tolerance under increased loads due to thermal expansion or other movement.
  • Evaluate the use and placement of sleepers or other components that mitigate the buckling of pipelines.
  • Evaluate the use of different surveying methods such as LIDAR to confirm pipeline systems remain within design tolerances throughout their service life.
  • Consider revisions to API RP 17V that include a section on subsea leak detection best practices.

Lessons learned

Gulf of America educational summary

The numbers were telling operators something was wrong for hours, but the team assumed a bad meter. A leak alarm that could never trip and no rule to shut in on unexplained discrepancies let a large release continue.

  • An unexplained flow or pressure mismatch is a possible leak until proven otherwise.
  • Check that alarm setpoints can actually activate under real conditions.
  • Post-hurricane restarts deserve extra scrutiny of subsea integrity.

Plain-language interpretation by Gulf of America. Not a finding of BSEE or any investigating authority.